 FC-73
www.firecontrolinstruments.com
DESCRIPTION
The FC-73 Series Fire Alarm Control panel is a proven, versatile conventional zoned unit which meets the requirements of NFPA Standard 72 for Central Station, Protected Premises, Auxiliary, Remote and Proprietary Supervising Station Fire Alarm Systems. It is listed to UL Standard 864; inherently power limited, and has all necessary circuitry to meet the UL transient immunity requirements. The system is housed in a heavy-duty steel enclosure finished in red, with panels displaying the status of vital functions. The surface mounted enclosure, with its slim appearance (4-inch depth), is designed to blend with any environment. The cabinet can house up to 7AH batteries while the system's power supply can maintain batteries of up to 33 AH batteries (enclosed in the separately available BC-1R, 11000654). The many features of the FC-73 provide a cost effective approach to system design, and allow a great degree of flexibility in one enclosure. The panel provides ten (10) Class "B" (Style B) or five (5) Class "A" (Style D) zones, expandable to twenty (20) Class "B" or ten (10) Class "A" zones with the addition of the ZDM-FC73 Module. The FC-73 also provides four (4) Class "B" (Style Y) or two (2) Class "A" (Style Z) notification appliance circuits. Standard on all FC-73 control panels are a City Master Box output, Polarity Reversal signaling connections, and Integrated DACT. The combination of a conventional fire alarm control panel with a microprocessor design allows for programming of many unique features such as time limit cutoff, programmed verification, pre-alarm delay, and cross-zoning. Individual zones can be assigned specific outputs and zone types such as alarm, supervisory or waterflow. In addition, up to eight (8) selectable/programmable notification appliance circuit output patterns are available for alternate styles of warnings. Programming is achieved through the LCD-FC73 annunciator module or through the Field Configuration Program (FCP-73). Supervision of vital components, modules, functional switches, and standby batteries is provided. The integral Digital Alarm Communicator Transmitter supports all standard reporting formats including: * 3/1, 1400 Hz * 3/1, 2300 Hz * SK 4/2, 1400 Hz * SIA 8 * SIA 20 * Contact ID Optional modules include an LCD remote annunciator, a zone expander module used to expand the system and a status display module which provides outputs and control functions for each zone as well as program access.
CONVENTIONAL FIRE ALARM CONTROL PANEL
FEATURES
*Individual Zone Disconnect Switches *Supports up to six (6) Remote LCD Displays * Supports up to six (6) Remote LED Annunciators * Integral Digital Communicator Transmitter * Expandable to Twenty (20) Class B or Ten (10) Class A Zones * Field Programmable Configuration * Eight (8) Selectable/Programmable Output Patterns Including Temporal Pattern Output per ANSI S3.41 *"Walk Test" Capability provided by the LCD-FC73 optional Remote Annunciator * Programmable Alarm Verification and Cross-Zoning * Four (4) Class B or Two (2) Class A Notification Appliance Circuits * Six (6) Amp power Supply * Three integral progammable relays * Provides Municipal Circuit or Reverse Polarity output * Reverse Polarity or Municipal Circuit output
S1869
An ISO 9001 Company
Specifications are provided for information only, and are not intended to be used for installation purposes and are believed to be accurate. However, no responsibility is assumed by Fire Control Instruments, Inc. for their use. Specifications subject to change without notice. (c) 2001 All Rights Reserved
.
9020-0523 Rev. B
Page 1 of 4
FC-73
www.firecontrolinstruments.com
the BASIC FC-73 ASSEMBLY
RING T IP 61 T 60 1 RING T IP 59 P1 58 RING T IP 57 T 56 2 RING T IP 55 P2 54
42 COM
ACK
S ILENCE
RES ET
DRILL
TT ES
43 NC
44 NO
45 COM
ALARM
S UPERVIS ORY
T ROUBLE
S ILENCED
POWER
46 NC
47 NO
48 COM
ZONE EXPANDER (ZDM-FC73) The ZDM-FC73 Zone Expander provides the FC-73 with ten (10) additional Class "B" (Style B) or five (5) Class "A" (Style D) initiating circuits. Mounts in main cabinet or in FC-2190 Accessory Cabinet.
49 NC
41 NO
38 39 40 + PR - MB +
36 37 + NAC1-
34 35 + NAC2-
28 PWR
29 GND
30 31 + NAC4-
32 33 + NAC3-
24 25 GND + 24DC
26 A
27 B
OPTIONAL ACCESSORIES
LCD-FC73 The LCD-FC73 supervised remote annunciator performs all system operations. It can be used for programming and provides access to the Walk Test feature and trouble and alarm information. The control panel can support up to six (6) annunciators. Total distance is up to 3000 feet away over two pair of two-conductor wire.
ALARM SUPERVISORY
RESET SILENCE
Specifications are provided for information only, and are not intened to be used for installation purposes, and are believed to be accurate. However, no responsibility is assumed by Fire Control Instruments, Inc. for their use. Specifications subject to change without notice.
16 Southwest Park, Westwood MA 02090 USA * Tel: 781-471-3000 * Fax: 781-471-3099 * www.firecontrolinstruments.com
9020-0523 Rev. B / Page 2 of 4
1 A 2 3 B Z1 C 4 D 5 A 6 7 B Z2 C 8 D 9 A 10 11 B Z3 C 12 D 13 A 14 15 B Z4 C 16 D 17 A 18 19 B Z5 C 20 D
21 B 22 23 EARTH W
ON
1 2 3 4
(R)
FIR CONT OL E R INS R ME S T U NT
FIRE ALARM CONT ROL MODEL FC-73
STATUS DISPLAY MODULE (FC-5280) The FC-5280 Status Display Module provides outputs and control functions for remote annunciation of alarm, trouble, and supervisory indications for each zone. The system can supervise up to eight (8) modules. The FC-5280 has ten (10) outputs for alarm and ten (10) for trouble annunciation. These outputs are "active low" (become negative when activated). Each output can provide up to 0.100 amp current, with a total of 0.700 amp available. The module has four (4), Form "C" relays that can be wired to operate with any of the outputs. The FC-5280 can be used to interface with an LED annunciator. It can be programmed to indicate alarm and trouble status for Zones 1 - 10, 11 - 20, or system status outputs. The FC-5280 mounts inside the FC73 cabinet.
NO 1C NO 3C NC
ON 1 2 3 4
B S BUS A
+ 24 GND 1 A+ 2 Z1 3 B - C- 4 D+ 5 A+ 6 Z3 7 B - C- 8 D+ 9 A+ 10 Z3 11 B - C- 12 D+ 13 A+ 14 Z4 15 B - C- 16 D+ 17 A+ 18 Z5 19 B - C- 20 D+
FIRE ALARM ANNUNCIATOR
TROUBLE SILENCED AC
MODEL LCD-FC73
NC NO 2C NC
NO 4C NC
.
1 4 7
2 5 8 0
3
C1 C2 A1 A2 A3 A4 A5 A6 A7 A8 A9 A10 T T T T T T T T T T C3 C4 1 2 3 4 5 6 7 8 9 10
-
+
6 9 #
A S BUS
B
ENTER
ACK
*
.
(c) 2001 All Rights Reserved
FIRE CONTROL INSTRUMENTS
FC-73
www.firecontrolinstruments.com
NAC DIS CONNE CT S CH WIT (T PICAL) Y
1 A 2 3 B Z1 C 4 D
Integral DACT Connections
RING T IP 61 T1 60 RING TIP 59 P1 58 RING TIP 57 T2 56 RING TIP 55 P2 54
ZONE DIS CONNE CT S CH WIT (T PICAL) Y
48 COM 47 NO 41 NO 42 COM 49 NC
10 Style B or 5 Style D Initiating Device Circuits Max. Voltage- 25.5 VDC Max. Circuit Resistance- 50 Ohms Total Alarm Current for all Circuits- 1.0 amp. Supervisory Current per Zone- 0.003 amp. Alarm Current per Zone- 0.095 amp. Power-Limited & Supervised with 3.9KW EOL (not required for Style D circuits)
ACK
S ILENCE
RESET
DRILL
TT ES
43 NC
44 NO
45 C OM 38 39 + PR 36 37 + NAC 1- 27 B 24 25 GND + 2 4DC 26 A 28 PWR 29 GND 30 31 + NAC4- 32 33 + NAC3 - 34 35 + NAC2 - 40 +
ALARM
S UPERVIS ORY
T ROUBLE
S ILENCED
POWER
3 Programmable Form C Relay Outputs 2.5 amps. @ 24 VDC/ 24 VAC (inductive) 5 amps. @ 24 VDC (resistive) Non power-limited
46 NC
5 A 6 7 B Z2 C 8 D 9 A 10 11 3 BZ C 12 D 13 A 14 15 4 BZ C 16 D 17 A 18 19 5 BZ C 20 D
ZONE 1
ZONE 11 ZONE 12
Municipal Circuit Output Reverse Polarity Output
NAC 1
ZONE 2 ZONE 3
NAC 2
ZONE 4 ZONE 5 ZONE 14
4 Style Y or 2 Style Z Notification Appliance Circuits Power-limited & Supervised with 3.9KW EOL resistor(Style Y only) 3.0 amps. max. out of any one circuit
NAC 3
ZONE 6 ZONE 7 ZONE 16 ZONE 17 ZONE 18 ZONE 19 ZONE 20
NAC 4
ZONE 8
SBUS & Auxliary Power 1.0 amp. max. @ 24 VDC
MAS ER T BOX
Connection to 120 VAC 3 amps. @ 60 Hz
21 B 22 23 EART HW
B S US B A
ZONE 9 ZONE 10
(R)
FIR CONT OL E R INS R MENT TU S
FIRE ALARM CONT ROL MODEL FC-73
NAC INDICAT ING LEDs GRE N= CIRCUITACT E IVE Y LLOW= CIRCUITT E ROUB LE T ICAL YP
ON 1 2 3 4
ZONE INDICAT ING LEDs RE ELLOW= ALARM/S RVIS Y OFF-NORMAL D/Y UPE OR Y LOW= ZONE T OUB EL R LE (T PICAL) Y
Specifications are provided for information only, and are not intended to be used for installation purposes and are believed to be accurate. However, no responsibility is assumed by Fire Control Instruments, Inc. for their use. Specifications subject to change without notice.
16 Southwest Park, Westwood MA 02090 USA * Tel: 781-471-3000 * Fax: 781-471-3099 * www.firecontrolinstruments.com
9020-0523 Rev. B / Page 3 of 4
+ 24 GND
Mounting Location for ZDM-FC73 or FC-5280 (ZDM-FC73 can mount remotely in FC-2190 Accessory Cabinet)
(c) 2001 All Rights Reserved
FIRE CONTROL INSTRUMENTS
FC-73
www.firecontrolinstruments.com
GENERAL SPECIFICATIONS
Primary AC Voltage Total DC Voltage output Auxiliary Power output Smoke Detector output Battery Charging Voltage Battery Charging Current Minimum Telephone input sensitivity Minimum Telephone line voltage Low Battery Threshold Low AC Brown-out Threshold Dimensions Shipping Weight 120 Vrms @ 60 Hz, 3A 6A 27.4 VDC @ 1A 27.4 VDC @ 1A 27.4 VDC 0.75A max. (33 A/H batteries max.) 35 dB 3V 20.4 VDC 98 VAC 16" W x 26.4" H x 4" D (40.64 x 67.06 x 10.16 cm) 28 lbs. 60 to 80 F (15 to 27 C), 32 to 120 F max. (0 to 49 C) not to exceed 85% @ 90F (32 C), non-condensing
ENVIRONMENTAL SPECIFICATIONS
Recommended Operating Temperature Range Recommended Operating Humidity Range
INITIATING DEVICE CIRCUIT SPECIFICATIONS
10 Style B (Class B) or 5 Style D (Class A) IDCs expandable to 20 Style B, 10 Style D withh addition of ZDM25.6 VDC FC73 50 ohms Maximum Voltage 1.0 amp. Maximum Circuit Resistance 0.003 amp. Maximum Alarm Current for all Zones 0.095 amp. Supervisory Current (per Zone) Alarm Current (per Zone) Supervised & Power-Limited
NOTIFICATION APPLIANCE CIRCUIT SPECIFICATIONS
4 Style Y (Class B) or 2 Style Z (Class A) NACs rated 3.0 amp. each (Note: total current draw from NACS, smoke detector power, auxiliary power and main Control Panel not to exceed 6.0 amp.) Supervised & Power-Limited
APPROVALS
U.L. (Std 864) C.S.F.M. S1869 Pending
ORDERING INFORMATION
Part No. 150-00013 150-00014 150-00015 150-00016 150-00018 150-00023 Model FC73-PCB FC-73 ZDM-FC73 LCD-FC73 FC-5280 FC-2190 Description FC-73 Main Board Fire Alarm Control Panel Zone Expander Module Remote Annunciator Status Display Module Accessory Cabinet
(c) 2001 All Rights Reserved
Specifications are provided for information only, and are not intended to be used for installation purposes and are believed to be accurate. However, no responsibility is assumed by Fire Control Instruments, Inc. for their use. Specifications subject to change without notice.
FIRE CONTROL INSTRUMENTS
16 Southwest Park, Westwood MA 02090 USA * Tel: 781-471-3000 * Fax: 781-471-3099 * www.firecontrolinstruments.com
9020-0523 Rev. B / Page 4 of 4


▲Up To Search▲   

 